🧮

Three Phase Power Calculator - Calculate Power, Current & Voltage

Calculate three-phase electrical power, current, and voltage with support for balanced and unbalanced loads. Free 3-phase power calculator with delta and wye configurations, power factor calculations, and electrical formulas.

System Configuration

Wye (Star) Configuration: Line voltage = √3 × Phase voltage. Common in distribution systems with neutral.

Electrical Parameters

V
A

Motor Efficiency (Optional)

%

Common System Voltages

Calculation Results

Line Voltage

480 V

Line Current

10 A

Phase Voltage

277.13 V

Phase Current

10 A

Power Analysis

Real Power (P)7.07 kW
Reactive Power (Q)4.38 kW VAR
Apparent Power (S)8.31 kW VA
Power Factor
0.85
Good
Phase Angle31.79°

Formulas Used

Three-Phase Power:

P = √3 × VL × IL × cos(φ)

Apparent Power:

S = √3 × VL × IL

Wye Relationships:

VL = √3 × VP

IL = IP

3-phase power calculator parameters

  • Voltage (V): Enter the phase-to-phase (VLLV_{LL}) voltage for a 3-phase AC supply in volts.
  • Current (I): Enter the current in Amperes (A).
  • Power factor (cos φ): Enter the power factor of the load. It is between 0 and 1.

How to calculate 3-phase power?

The 3-phase power formula for active power is:

PkW=3VLLIcosϕ1000P_{kW} = \frac{\sqrt{3} \cdot V_{LL} \cdot I \cdot \cos \phi}{1000}

Where,

  • VLLV_{LL} is the 3-phase line voltage,
  • II is the current, and
  • cosϕ\cos \phi is the power factor between 0 and 1.

The 3-phase power formula for apparent power is:

SkVA=3VLLI1000S_{kVA} = \frac{\sqrt{3} \cdot V_{LL} \cdot I}{1000}

Where,

  • VLLV_{LL} is the 3-phase line voltage, and
  • II is the current.

The 3-phase power formula for reactive power is:

Qkvar=3VLLIsinϕ1000Q_{kvar} = \frac{\sqrt{3} \cdot V_{LL} \cdot I \cdot \sin \phi}{1000}

Where,

  • sinϕ=1(cosϕ)2\sin \phi = \sqrt{1 - (\cos \phi)^2}, and
  • cosϕ\cos \phi is the power factor between 0 and 1.

An alternative 3-phase power formula for reactive power is:

Qkvar=SkVA2PkW2Q_{kvar} = \sqrt{S_{kVA}^2 - P_{kW}^2}

Where,

  • SkVAS_{kVA} is the 3-phase apparent power, and
  • PkWP_{kW} is the 3-phase active power.

⚠️ Electrical Safety Warning

Before Working with Three-Phase Systems

  • • Always turn off power and verify with meters
  • • Follow lockout/tagout procedures
  • • Use appropriate PPE (arc flash protection)
  • • Verify phase sequence before connecting motors
  • • Have qualified electricians perform installations

Three-Phase Hazards

  • • High voltages (208V-600V+) can be lethal
  • • High fault currents can cause arc flash
  • • Motors can start unexpectedly
  • • Neutral loss in Wye systems creates hazards
  • • Wrong phase rotation can damage equipment

Frequently Asked Questions

What is three-phase power and how is it calculated?

Three-phase power is electrical power transmitted using three alternating current waveforms, each 120° out of phase. For balanced loads: P = √3 × VL × IL × cos(φ), where VL is line voltage, IL is line current, and cos(φ) is the power factor. This provides more efficient power transmission than single-phase systems.

What's the difference between Delta and Wye (Star) configurations?

In Delta configuration, loads are connected in a triangle with line voltage equal to phase voltage (VL = VP). In Wye (Star) configuration, loads connect to a common neutral point with line voltage = √3 × phase voltage (VL = √3 × VP). Wye provides a neutral point and is common in distribution systems.

How do I calculate three-phase motor current?

For a three-phase motor: I = P / (√3 × V × cos(φ) × η), where P is motor power (watts), V is line voltage, cos(φ) is power factor (typically 0.8-0.9 for motors), and η is motor efficiency (typically 85-95%). This gives you the line current needed for proper wire sizing.

What is power factor and why is it important?

Power factor (cos φ) is the ratio of real power to apparent power, ranging from 0 to 1. It indicates how efficiently electrical power is used. Low power factor (below 0.85) results in higher current draw, increased losses, and utility penalties. Motors, transformers, and fluorescent lights typically have lagging power factors.

How do balanced and unbalanced loads affect calculations?

Balanced loads have equal impedance on all three phases, allowing simpler calculations using standard formulas. Unbalanced loads require individual phase calculations and can cause neutral current in Wye systems. Unbalanced systems are less efficient and can cause equipment problems.

What safety considerations apply to three-phase electrical work?

Three-phase systems involve high voltages and currents that can be lethal. Always: turn off power and verify with meters, follow lockout/tagout procedures, use proper PPE, ensure proper grounding, verify phase sequence for motors, and have qualified electricians perform installations. Never work on live three-phase equipment without proper training.

Related Tools